D-Lock - Structural Performance
SUBSECTIONS: Overview . BENEFITS . CONSTRUCTION . PERFORMANCE . APPLICATIONS
Panel type |
BSEN 12825
classification |
Ultimate load |
Uniformly distributed load |
D-Lock 30 |
1/A/3/2 |
In excess of 4kN |
7.5kN/m2 |
D-Lock 38 |
2/A/3/2 |
In excess of 6kN |
10kN/m2 |
The above info is based on testing in compliance with the BSEN 12825 specification. The classifications shown are based on a deflection under working load not exceeding 2.5mm and a safety factor of 3.
Uniformly distributed loads are shown for information as they do not form part of BSEN 12825. However the figures shown are based on testing in accordance with BSEN 12825.
Finished floor heights from 60mm to 1000mm are available using one of our standard pedestals. For heights outside of this range alternative pedestals are available.
The classifications given are based on the use of the Kingspan range of pedestals.